YKуY, NYM, NYY

Standart: HD 603 S1: 1994/A3:2007, EN 60332-1-2:2004/A:2015
  • Cables YKуY, NYM, NYY refer to power flexible cables with copper conductors, PVC insulation and sheath.
  • They are used in conditions with a high probability of strong bends of conductors.
  • Designed for the transmission and distribution of electrical energy in stationary installations for a rated alternating voltage of 0.66; 1 kV with a frequency of 50 Hz.
  • They are used when laying in blocks, on specialized cable tray systems, can be used in industrial premises, distribution and lighting devices, as well as in ordinary residential premises as electrical wiring, in conditions requiring cable bends.
Minimum service life is 30 years
Guaranteed service life is 5 years
Minimum bending radius Single-conductor cable: 10 x outer diameter
Multi-conductor cable: 7.5 x outer diameter
Temperature range installation: not below -15°С
operation: from -50°С to +50°С
Design
Conductors: copper multi-wire of the 5th flexibility class (class 5 DSTU EN 60228)
Insulation: PVC compound
Armor: no
Rated voltage, kV
0,66 1
Number of conductors Nominal cross-section area of the key conductors, mm2
1 1,5 — 50 1,5 — 400
2, 3, 4 1,5 — 50 1,5 — 300
5 1,5 — 50 1,5 — 240
 
Certifications
Detailed description

YKуY, NYM, NYY cables are power flexible cables of increased flexibility. They are designed for the transmission and distribution of electrical energy in stationary installations for a rated alternating voltage of 0.66; 1 kV with a frequency of 50 Hz.

Design

According to the degree of flexibility, cables are divided into 6 categories, from 1 to 6. The higher the category, the more flexibility.

Structurally, YKуY, NYM, NYY consist of copper multi-wire conductors. The number of conductors varies from 1 to 5, with a cross-section from 1.5 mm² to 400 mm². The conductors are protected by PVC insulation and sheath. The insulation of the conductors is color-coded for easy identification during installation. YKуY, NYM, NYY belong to the class of cables resistant to flame propagation when laid in bundles.

Operation

The cables are designed for operation at temperatures from -50°C to +50°C. They are suitable for laying in a humid environment – up to 98% relative humidity at temperatures up to +35°C. The laying without preheating is allowed at a temperature not lower than -15°C.

The minimum bend radius during installation must be at least 10 outer cable diameters for a single-conductor cable and 7.5 outer cable diameters for a multi-conductor cable.

YKуY, NYM, NYY can withstand long-term heating of conductors up to 70°C during operation. The maximum allowable temperature at short-circuit currents is 160°С, and in an emergency mode no more than 80°С.

The service life of the cables is at least 30 years. The guaranteed service life is 5 years.

On the website of EUROPAN LLC you can select and buy YKуY, NYM, NYY cables that meet high-quality standards, confirmed by the relevant certificates. They are time-tested and have earned a reputation as a high-quality and reliable product in operation, allowing you to create electrical power networks that withstand frequent and pronounced bends. Our managers are always ready to advise you on technical characteristics, prices and order conditions.

Read more

Permissible short circuit currents of cables

Nominal conductor cross-section, mm²

Permissible current of one-second short circuit of cables, kA

Nominal conductor cross-section, mm²

Permissible current of one-second short circuit of cables, kA

1,5 0,17 120 13,21
2,5 0,27 150 16,30
4,0 0,43 185 20,39
6,0 0,65 240 26,80
10 1,09 300 33,49
16 1,74 400 39,60
25 2,78 500 49,50
35 3,86 625 62,37
50 5,23 800 79,20
70 7,54 1000 99,00
95 10,48

 

 