KVVGz, KVVGzng, KVVGzngd

TU U 27.3-39543889-005:2019; The National Standards of Ukraine HD 627 S1:2012
  • KVVGz, KVVGzng, KVVGzngd are control cables with copper conductors, PVC insulation and sheath, with filling
  • They are designed for fixed connection to electrical devices, apparatuses, terminal block jumpers of electrical switchgears with a rated alternating voltage up to 660 V, a frequency up to 100 Hz or a constant voltage up to 1000 V.
  • They are laid in conditions where there is a need of the cable gland at the input to electrical equipment. They are used for laying in rooms, channels, tunnels, in an aggressive environment, provided there is no mechanical stress on the cable. They can be laid outdoors, provided they are protected from mechanical damage and exposure to direct sunlight. The laying in the ground (in trenches) is allowed while ensuring the protection of the cable at the points of exit to the surface.
Minimum service life is - 20 years when laid in the ground (in trenches) and on overpasses, provided the cables are protected from ultraviolet radiation;
- 25 years when laid in rooms, tunnels, channels
Guaranteed service life is 3 years
Minimum bending radius when laying at an ambient temperature not lower than 0°С, not less:
- 3 x outer diameter - for cables with outer diameter up to 10 mm inclusive;
- 4 x outer diameter - for cables with an outer diameter over 10 to 25 mm inclusive;
- 6 x outer diameter - for cables with outer diameter over 25 mm
Temperature range installation: not below -15°С
operation: -50°С to +50°С
Interpretation of cables KVVGz, KVVGzng, KVVGzngd

The copper conductor;

K – control cable;

V – PVC compound insulation of conductors;

V – PVC compound outer sheath;

G – without armor («bare»);

z – filling of the inter-conductors space;

«ng» – does not support combustion;

«ngd» – does not support combustion, with reduced smoke and gas emission.

Design
Conductors: copper single-wire (class 1 DSTU EN 60228)
Insulation: PVC compound
Armor: no
Number of conductors Nominal cross-section area of the key conductors, mm2
2, 3, 4, 5, 7, 10, 14, 19, 27, 37 0,75; 1,0; 1,5; 2,5
4, 5, 7, 10, 14, 19 4,0; 6,0; 10
 
Fire safety
  • The National Standards of Ukraine 4809:2007
  • KVVGz - PB 1XXXXXXXX
  • KVVGzng - PB 12XXXXXXX
  • KVVGzngd - PB 122111XXX
Certifications
Detailed description

KVVGz, KVVGzng, KVVGzngd are control cables with copper conductors, PVC insulation and sheath, with filling. They are designed for fixed connection with the electrical equipment with a rated alternating voltage up to 660 V and a frequency up to 100 Hz or a constant voltage up to 1000 V.

Applicability scope

Control cables KVVGz, KVVGzng, KVVGzngd are mainly used in conditions where there is a need of the cable gland at the input to electrical equipment, and for single laying in cable structures and rooms. They are also widely used in tunnels, channels, high-altitude areas, outdoors in an aggressive environment, provided there is no risk of mechanical damage and the cables are protected from the direct sunlight. The laying in earth trenches is allowed, provided that the cable is protected at the points of exit to the surface. The group laying is allowed only in outdoor electrical installations and industrial premises using additional passive fire protection equipment.

Cable types with letter indices «ng» and «ngd» are used in conditions of the increased risk of a fire, and can also be used for group laying. The «ng» index indicates that the KVVGzng cable does not spread combustion. And the index «ngd» denotes that KVVGzngd cable does not support combustion and has a low level of smoke emission in the event of a fire.

Design

The design of KVVGz consists of several isolated from each other single-wire copper conductors of the 1st flexibility class (class 1 of DSTU 60288), with the number from 4 to 37. The conductors are covered with a layer of PVC compound, stranded together and are color-coded or digitally marked. Each layer contains a marker pair of conductors, which differ in color from the rest of the conductors and from each other. The insulated conductors are encased in a PVC sheath, and the gaps between them are filled with PVC or nonvulcanized rubber compound, which gives the cable an almost round shape.

You can get more detailed information about the cable design, as well as help in choosing the most suitable solution, taking into account the permissible load power, individual wishes and laying conditions, from the managers of EUROPAN LLC.

Operation

The operating temperatures of KVVGz, KVVGzng, KVVGzngd ranges from -50°C to +50°C. At the same time, the installation without preheating is possible at a temperature not lower than -15°C. The maximum permissible air humidity at which the cable performs its functions is 98% at a temperature of +35°C.

Long-term permissible heating of conductor during operation should not exceed +70°С.

In order to avoid damage to the cable during installation, one must observe the permissible bend radius of the conductor, which in turn depends on the cable diameter and the ambient temperature. Thus, when laying KVVGz at an air temperature of at least 0°C, the bend radius is at least:

– 3 cable diameters – for cables with outer diameter up to 10 mm inclusive;

– 4 cable diameters – for cables with an outer diameter over 10 to 25 mm inclusive;

– 6 cable diameters – for cables with outer diameter over 25 mm.

Provided the proper installation and operation, the service life of the conductor is at least 20 years from the date of manufacture when laying in earth trenches and on overpasses, subject to protection from ultraviolet radiation, and at least 25 years when laying in rooms, tunnels, channels. The guaranteed service life is 3 years.

On the website of EUROPAN LLC you can select and buy a high-quality control cable KVVGz, certified in accordance with the legislation of Ukraine. You may also find various options for its execution – KVVG and KVVGE. Our managers will advise you on any issues related to the order, help you choose the necessary products, or provide a ready-made solution for your technical requirements. For consultation, you can use the contact information on our website.

Read more
Nomenclature and mass-dimensional characteristics

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
2 x 0,75 6,7 64
3 x 0,75 7,1 74
4 x 0,75 7,6 87
5 x 0,75 8,3 104
7 x 0,75 9,5 140
10 x 0,75 11,7 200
14 x 0,75 12,6 244
19 x 0,75 13,9 307
27 x 0,75 16,3 421
37 x 0,75 18,6 557
2 x 1,0 7,1 73
3 x 1,0 7,4 85
4 x 1,0 8,0 102
5 x 1,0 9,3 135
7 x 1,0 10,0 165
10 x 1,0 12,3 235
14 x 1,0 13,3 291
19 x 1,0 14,7 369
27 x 1,0 17,3 508
37 x 1,0 19,7 674
2 x 1,5 7,6 89
3 x 1,5 7,9 106
4 x 1,5 9,2 140
5 x 1,5 10,0 168
7 x 1,5 10,7 208
10 x 1,5 13,3 299
14 x 1,5 14,4 374
19 x 1,5 15,9 479
27 x 1,5 19,3 682
37 x 1,5 21,5 884
2 x 2,5 8,4 118
3 x 2,5 9,4 158
4 x 2,5 10,2 191
5 x 2,5 11,0 231
7 x 2,5 11,9 291
10 x 2,5 14,9 421
14 x 2,5 16,1 535
19 x 2,5 17,9 692
27 x 2,5 21,7 985
37 x 2,5 24,7 1313
4 x 4,0 11,8 273
5 x 4,0 12,8 334
7 x 4,0 13,9 424
10 x 4,0 17,6 617
14 x 4,0 19,5 811
19 x 4,0 21,6 1052
4 x 6,0 13,0 370
5 x 6,0 14,2 454
7 x 6,0 15,5 584
10 x 6,0 20,0 870
14 x 6,0 21,7 1125
19 x 6,0 24,6 1492
4 x 10 15,9 579
5 x 10 17,4 714
7 x 10 19,5 945
10 x 10 25,2 1405
14 x 10 27,4 1824
19 x 10 30,6 2389

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
2 x 0,75 6,7 66
3 x 0,75 7,1 76
4 x 0,75 7,6 89
5 x 0,75 8,3 107
7 x 0,75 9,5 143
10 x 0,75 11,7 204
14 x 0,75 12,6 249
19 x 0,75 13,9 312
27 x 0,75 16,3 427
37 x 0,75 18,6 565
2 x 1,0 7,1 75
3 x 1,0 7,4 88
4 x 1,0 8,0 104
5 x 1,0 9,3 138
7 x 1,0 10,0 168
10 x 1,0 12,3 240
14 x 1,0 13,3 296
19 x 1,0 14,7 374
27 x 1,0 17,3 515
37 x 1,0 19,7 682
2 x 1,5 7,6 91
3 x 1,5 7,9 108
4 x 1,5 9,2 144
5 x 1,5 10,0 172
7 x 1,5 10,7 212
10 x 1,5 13,3 305
14 x 1,5 14,4 380
19 x 1,5 15,9 485
27 x 1,5 19,3 690
37 x 1,5 21,5 893
2 x 2,5 8,4 121
3 x 2,5 9,4 161
4 x 2,5 10,2 195
5 x 2,5 11,0 235
7 x 2,5 11,9 295
10 x 2,5 14,9 427
14 x 2,5 16,1 542
19 x 2,5 17,9 699
27 x 2,5 21,7 995
37 x 2,5 24,7 1325
4 x 4,0 11,8 278
5 x 4,0 12,8 339
7 x 4,0 13,9 430
10 x 4,0 17,6 626
14 x 4,0 19,5 820
19 x 4,0 21,6 1062
4 x 6,0 13,0 375
5 x 6,0 14,2 459
7 x 6,0 15,5 590
10 x 6,0 20,0 880
14 x 6,0 21,7 1135
19 x 6,0 24,6 1504
4 x 10 15,9 586
5 x 10 17,4 722
7 x 10 19,5 954
10 x 10 25,2 1421
14 x 10 27,4 1839
19 x 10 30,6 2406

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
2 x 0,75 6,7 70
3 x 0,75 7,1 81
4 x 0,75 7,6 95
5 x 0,75 8,3 114
7 x 0,75 9,5 153
10 x 0,75 11,7 218
14 x 0,75 12,6 265
19 x 0,75 13,9 332
27 x 0,75 16,3 454
37 x 0,75 18,6 600
2 x 1,0 7,1 80
3 x 1,0 7,4 93
4 x 1,0 8,0 111
5 x 1,0 9,3 147
7 x 1,0 10,0 178
10 x 1,0 12,3 255
14 x 1,0 13,3 313
19 x 1,0 14,7 396
27 x 1,0 17,3 544
37 x 1,0 19,7 721
2 x 1,5 7,6 97
3 x 1,5 7,9 115
4 x 1,5 9,2 152
5 x 1,5 10,0 182
7 x 1,5 10,7 224
10 x 1,5 13,3 321
14 x 1,5 14,4 400
19 x 1,5 15,9 510
27 x 1,5 19,3 725
37 x 1,5 21,5 937
2 x 2,5 8,4 128
3 x 2,5 9,4 170
4 x 2,5 10,2 205
5 x 2,5 11,0 248
7 x 2,5 11,9 309
10 x 2,5 14,9 447
14 x 2,5 16,1 565
19 x 2,5 17,9 728
27 x 2,5 21,7 1037
37 x 2,5 24,7 1379
4 x 4,0 11,8 291
5 x 4,0 12,8 355
7 x 4,0 13,9 448
10 x 4,0 17,6 653
14 x 4,0 19,5 854
19 x 4,0 21,6 1104
4 x 6,0 13,0 390
5 x 6,0 14,2 479
7 x 6,0 15,5 612
10 x 6,0 20,0 914
14 x 6,0 21,7 1175
19 x 6,0 24,6 1556
4 x 10 15,9 609
5 x 10 17,4 751
7 x 10 19,5 988
10 x 10 25,2 1474
14 x 10 27,4 1902
19 x 10 30,6 2484