AKVBbSHv, AKVBbSHvng, AKVBbSHvngd

TU U 27.3-39543889-005:2019, The National Standards of Ukraine HD 627 S1:2012
  • AKVBbSHv, AKVBbSHvng, AKVBbSHvngd are armoured control cables with aluminum conductors, PVC compound insulation, armor of two galvanized steel bands and a PVC compound protective hose.
  • They are designed for the fixed connection to electrical devices, apparatuses, terminal block jumpers of electrical switchgears with a rated alternating voltage up to 660 V, frequency up to 100 Hz or constant voltage up to 1000 V.
  • They are used for laying in rooms, channels, tunnels, in the ground (in trenches), including in an aggressive environment and in places exposed to leakage currents, if the cable is not subjected to significant tension strain. They can be laid outdoors, provided they are protected from mechanical damage and exposure to direct sunlight.
Minimum service life is - 20 years when laid in the ground (in trenches) and on cable tray systems, provided they are protected from ultraviolet radiation;
- 25 years when laying in rooms, tunnels, channels
Guaranteed service life is 3 years
Minimum bending radius 10 x outer diameter
Temperature range installation: not below -7°С
operation: from -50°С to +50°С
Interpretation of cables AKVBbSHv, AKVBbSHvng, AKVBbSHvngd

A – aluminum conductor;

K – control cable;

V – PVC insulation;

B – armor made of two galvanized steel bands;

b – without bedding under armor;

SHv – protective hose of PVC compound; 

«ng» – does not support combustion;

«ngd» – does not support combustion, with reduced smoke and gas emission.

Design
Conductors: aluminum single-wire (class 1 DSTU EN 60228)
Insulation: PVC compound; the sheath is made of protective hose of PVC compound
Armor: two galvanized steel bands
Number of conductors Nominal cross-section area of the key conductors, mm2
4, 5, 7, 10, 14, 19, 27, 37 2,5
4, 5, 7, 10, 14, 19 4,0; 6,0; 10
 
Fire safety
  • The National Standards of Ukraine 4809:2007
  • AKVBbSHv - PB 1XXXXXXXX
  • AKVBbSHvng - PB 12XXXXXXX
  • AKVBbSHvngd - PB 122111XXX
Certifications
Detailed description

AKVBbSHv, AKVBbSHvng, AKVBbSHvngd are armoured control cables with aluminum conductors, PVC compound insulation, armor of two galvanized steel bands and a PVC compound protective hose. They are designed for the fixed connection to electrical devices, apparatuses, terminal block jumpers of electrical switchgears with a rated alternating voltage up to 660 V, a frequency up to 100 Hz or a constant voltage up to 1000 V.

Applicability scope

AKVBbSHv is used in various climatic conditions, it is resistant to temperature extremes, corrosion and precipitation. It can be used in places with high humidity, as well as in structures, industrial premises, tunnels and channels. The armor protects the cable from mechanical damage – shock, vibration, rodent bites. Due to this, AKVBbSHv is actively used for laying in earth trenches, as well as in places exposed to leakage currents, if it is not subjected to significant tension strain. The cable is not bend resistant, therefore it is not used in places where the strong tension is required. It can be laid outdoors, provided it is protected from mechanical damage and exposure to direct sunlight.

 Design

The design of AKVBbSHv is based on an aluminum single-wire conductor of the 1st flexibility class (class 1 of DSTU EN 60288). Each conductor is insulated with PVC compound. The number of conductors varies from 4 to 37. The insulated conductors are stranded, the marker pair of conductors is distinctively colored or digitally marked. The armor is made of two galvanized steel bands. And the hermetic sheath is made in the form of a PVC compound protective hose.

In case of a single laying, AKVBbSHv does not spread combustion. At the same time, there are cable types with a PVC compound sheath of low flammability. They are marked with letter indices «ng» which means that such cable does not support combustion, and «ngd» – the cable does not support combustion and has reduced smoke and gas emission. AKVBbSHvng and AKVBbSHvngd can be used for bundle laying, in places where additional protection of cable circuits and special fire-prevention measures are required.

You can get more detailed information about the cable design from the experts of EUROPAN LLC, as well as advice on how to select the weight and diameter of the conductor, taking into account the load power.

 Operation

AKVBbSHv, AKVBbSHvng, AKVBbSHvngd can be used at temperatures from -50°C to +50°C. At the same time, the installation without preheating is allowed at a temperature not lower than -7°C. The maximum permissible air humidity at which the cable remains sufficient is 98% at a temperature of +35°C.

The bend radius during laying is at least 10 outer cable diameters. In this case the armor completely covers the stranded conductors.

The maximum long-term permissible heating of conductors during operation should not exceed +70°С.

The correct installation and operation ensure the following service life of the cable:

at least 20 years when laying in the ground and on overpasses, provided they are protected from direct sunlight; and at least 25 years – when laying in rooms, tunnels and channels.

The guaranteed service life is 3 years.

The website of EUROPAN LLC presents armoured cables AKVBbSHv and KVBbSHv of various cross-sections made by the reliable domestic manufacturer. The high quality of the products is evidenced by the certificates of conformity. In addition, on the website you can familiarize yourself with other cable and wire products for various purposes. Our managers will help you to gain insight on the variety of products and select a conductor of the required cross-section, taking into account the needs, laying conditions, and load power.

Read more
Nomenclature and mass-dimensional characteristics

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
4 x 2,5 13,4 288
5 x 2,5 14,5 335
7 x 2,5 15,4 378
10 x 2,5 18,4 489
14 x 2,5 19,8 573
19 x 2,5 21,5 681
27 x 2,5 25,6 907
37 x 2,5 28,1 1103
4 x 4,0 15,2 362
5 x 4,0 16,3 414
7 x 4,0 17,4 473
10 x 4,0 21,2 623
14 x 4,0 22,7 738
19 x 4,0 25,4 927
4 x 6,0 16,5 421
5 x 6,0 17,7 487
7 x 6,0 19,1 572
10 x 6,0 23,3 745
14 x 6,0 25,6 933
19 x 6,0 28,0 1131
4 x 10 19,5 572
5 x 10 21,1 661
7 x 10 22,7 774
10 x 10 28,6 1080
14 x 10 31,0 1332
19 x 10 34,6 1672

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
4 x 2,5 13,4 294
5 x 2,5 14,5 342
7 x 2,5 15,4 386
10 x 2,5 18,4 499
14 x 2,5 19,8 584
19 x 2,5 21,5 693
27 x 2,5 25,6 923
37 x 2,5 28,1 1120
4 x 4,0 15,2 369
5 x 4,0 16,3 423
7 x 4,0 17,4 482
10 x 4,0 21,2 634
14 x 4,0 22,7 751
19 x 4,0 25,4 943
4 x 6,0 16,5 429
5 x 6,0 17,7 496
7 x 6,0 19,1 583
10 x 6,0 23,3 758
14 x 6,0 25,6 949
19 x 6,0 28,0 1149
4 x 10 19,5 583
5 x 10 21,1 673
7 x 10 22,7 786
10 x 10 28,6 1098
14 x 10 31,0 1352
19 x 10 34,6 1696

Select rated voltage, kV

Number of conductors and nominal cross-section, mm2

Nominal outer diameter, mm

Estimated weight of 1 km of cables, kg
4 x 2,5 13,4 309
5 x 2,5 14,5 360
7 x 2,5 15,4 405
10 x 2,5 18,4 525
14 x 2,5 19,8 615
19 x 2,5 21,5 731
27 x 2,5 25,6 975
37 x 2,5 28,1 1185
4 x 4,0 15,2 388
5 x 4,0 16,3 445
7 x 4,0 17,4 507
10 x 4,0 21,2 668
14 x 4,0 22,7 791
19 x 4,0 25,4 996
4 x 6,0 16,5 450
5 x 6,0 17,7 521
7 x 6,0 19,1 611
10 x 6,0 23,3 796
14 x 6,0 25,6 998
19 x 6,0 28,0 1209
4 x 10 19,5 611
5 x 10 21,1 708
7 x 10 22,7 826
10 x 10 28,6 1155
14 x 10 31,0 1423
19 x 10 34,6 1787