{"id":4896,"date":"2020-07-20T03:29:05","date_gmt":"2020-07-20T00:29:05","guid":{"rendered":"https:\/\/europan.ua\/akvvg-akvvgng-akvvgngd\/"},"modified":"2023-10-05T14:35:37","modified_gmt":"2023-10-05T11:35:37","slug":"akvvg-akvvgng-akvvgngd-2","status":"publish","type":"page","link":"https:\/\/europan.ua\/en\/produkciya\/control-cables\/akvvg-akvvgng-akvvgngd-2\/","title":{"rendered":"AKVVG, AKVVGng, AKVVGngd"},"content":{"rendered":"

Cables AKVVG, AKVVGng, AKVVGngd<\/span><\/strong> refer to the control cables. These are cables with an aluminum conductor, PVC insulation and sheath. The are designed for stationary connection to electrical devices, apparatuses, terminal block jumpers of electrical switchgear with a rated alternating voltage up to 660 V, frequency up to 100 Hz or a constant voltage up to 1000 V.<\/p>\n

Applicability scope<\/strong><\/h5>\n

AKVVG, AKVVGng, AKVVGngd are mainly used for single laying in cable structures and rooms. They are also widely used in tunnels, chnnels, high mountain areas and outdoors in aggressive environments, provided there is no risk of mechanical damage and exposure to direct sunlight. The group laying is allowed only in outdoor electrical installations and industrial premises using additional passive fire protection equipment. The laying in the ground (in trenches) is allowed if the cable is protected at the points of exit to the surface.

The types of AKVVG with letter indices \u00abng\u00bb and \u00abngd\u00bb are used in places of increased fire hazard, as well as for laying in bundles. The \u00abng\u00bb marking indicates that the AKVVGng cable does not spread combustion. And the \u00abngd\u00bb index indicates that the AKVVGngd cable does not support combustion and has a low level of smoke emission in the event of a fire.<\/p>\n

Design<\/strong><\/h5>\n

The design of AKVVG consists of several insulated aluminum single-wire conductors of the 1st flexibility class (class 1 of DSTU EN 60228). The number of conductors varies from 4 to 37. The insulated conductors are stranded together and color-coded or numerically marked. Each conductor is covered with a layer of PVC compound. The upper outer sheath of the cable is made of the same material. The special PVC of low ignition, which is used for AKVVGng and AKVVGngd cables, allows them to be laid in bundles.<\/p>\n

You can contact the experts of EUROPAN LLC<\/a> and get more detailed information about the design of the cable, as well as consultation on the selection of the weight and diameter of the conductor, taking into account the load power.<\/p>\n

Operation<\/strong><\/h5>\n

The operating temperature of AKVVG, AKVVGng, AKVVGngd ranges from -50\u00b0C to +50\u00b0C. The maximum air humidity reaches 98% at a temperature of +35\u00b0\u0421. The installation process does not need the preheating\u00a0 at a temperature more than -15\u00b0C.<\/p>\n

The minimum bend radius during installation must be at least 6 outer cable diameters.<\/p>\n

The long-term permissible conductor heating temperature during operation is +70\u00b0C.<\/p>\n

The service life of the conductor is:<\/p>\n